This GRUNDIG UV5A Owner Manual is not only an instruction manual but a total functional circuit description of the Multimeter and includes circuit diagram at the end pages. It is very helpful for repairing and calibrating the instrument. It is written in two languages English and German for international support. It was very easy to repair my unit with this document. Regards, Regis Pauly, Electrical Engineer.
 ;
The owner's manual was evetything I thought it would be. I was able to print it out using both sides of the paper in quick order, saving me a search online for a used one.
 ;
Хорошее качество сканирования.
Мануал пришел часов эдак через 12. В целом доволен.
 ;
Fantastic quality and impressive delivery time. Based on this manual, I recommend this service without hesitation! Five Stars for certain.
 ;
Was happy to find the complete owners manual... It's all in there, just like the original...
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current. Temp. difference : approx. 0°C Current : less than 80% of rated current Temp. Difference Temp. difference : approx. 8°C Current : less than 80% of rated current � All amount of refrigerant leaked out. Check refrigeration cycle.
� Refrigerant leakege Clog of refrigeration cycle Defective compressor
Operating Current
Temp. difference : less than 8°C Current : over the reated current
� Excessive amount of refrigerant
Temp. difference : over 8°C
� Normal
Notice : Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal valve) High Higher Normal
Cause of Trouble Defective compressor Defective 4-way reverse valve Excessive amount of refrigerant Insufficient amount of refrigerant (Leakage) Clogging
Description Current is low. High pressure does not quickly rise at the beginning of operation. Current is low. Current is low.
Lower
Higher
Notice : 1. The suction pressure is usually 4.5~6.0 kg/cm2G(Cooling) at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
- 50 -
|
|
 |
> |
|