I recently purchased a manual for a Samsung DLP tv to help with a trouble shooting problem I was having. Every tv repair shop wanted close to $400.00 for the fix, but after I found Owner-Manuals.com I hit pay dirt. The manual they had for me to purchase and download was a complete service manual for the exact tv I needed. It was complete with wiring diagrams, schematics, and even part numbers. If your the fix it yourself type I highly recommend trying to find any manual here before paying someone else to fix whatever problem your having.
Outstanding quality manual. This is the exact documentation I needed to service my AKAI GX-210D. This is a PERFECT COPY of the service manual for my machine. Outstanding service. Thank-you!
This service manual have great value... Recommended A+++++++
Text excerpt from page 22 (click to view)
RI/RO-189W RI/RO-249W
For RI-189W/RO-189W
CHARACTERISTIC OF TH1 & TH2 K
The room is not cooled at all or not cooled. The compressor does not operate.
180 160 140
Push the button "TEST RUN" on the indoor unit, and wait 3 minutes.
120 100 80
Using a tester, measure voltage at the terminals on the terminal board.
60 40 20 0 -10 0 10 20 Fig. 1
10�C 30K
30 40�C
Is the voltage between terminal "N" and "1" of the terminal board the power supply voltage ?
NO
Replace the PWB ass'y with a new one. YES
Measure resistances of TH1 and TH2.
Are the resistances conformed Fig. 1 ?
NO
YES
Replace the thermistor ass'y with a new one.
The control circuit is normal. The compressor may be defective. The running capacitor may be defective. Refrigerant may be leaked. The outdoor fan motor may be defective. The outdoor fan motor capacitor may be defective.